| Radiators
|
CAST IRON COLUMN
|
|

|
- Cast iron sections
- Strong, long life and easy cleaning
- Easy grouping, assembly and cleaning
- Elegant lines
- Modern design
- Paint ability feature
- Maximum thermal power, maximum efficiency
- Superior quality and reliability
- Compliance to TS EN 442 1-2-3 and DIN EN 442 1-2-3 standards and TSE conformity.
|
|
Column Type Cast Iron Radıators |
Technical Data ( Per Section ) |
TYPE |
DIMENSIONS |
Nipple Size (İnch) |
Water Content (l/sect ) |
Heating Surface (m²) |
Weight (kg/sect) |
Heat Output * |
A ( mm ) |
B ( mm ) |
C ( mm ) |
D ( mm ) |
( watt / sect ) |
( kcal / sect ) |
4 / 65 |
600 |
500 |
144 |
60 |
1 ¼ " |
0,85 |
0,210 |
5,40 |
87,0 |
74,8 |
4 / 75 |
700 |
602 |
146 |
60 |
1 ¼ " |
0,97 |
0,250 |
6,38 |
103,0 |
88,5 |
4 / 95 |
899 |
800 |
144 |
60 |
1 ¼ " |
1,10 |
0,320 |
7,72 |
128,0 |
110,0 |
6 / 48 |
422 |
350 |
221 |
60 |
1 ¼ " |
0,85 |
0,230 |
6,06 |
94,0 |
80,8 |
6 / 65 |
600 |
500 |
221 |
60 |
1 ¼ " |
1,20 |
0,320 |
7,92 |
128,0 |
110,0 |
| * Heat output is given for 70 o C mean water temperature ( 75/65 o C) and 20 o C room temperature |
| * Tested according to EN 442 |
|
Type |
Heating Medium |
Max. Operating Pressure* ( atu ) |
Max. Operating Temperature ( °C ) |
Test Pressure ( Cold Water ) ( atu ) |
Gasket |
Normal |
Hot Water |
4 |
110 |
11-13 |
Manilla** |
Steam |
2 |
133 |
Klinger - SIL** |
High Pressure |
Warm or Hot Water |
6 |
140 |
11-13 |
Klinger - SIL** |
Steam |
4 |
151 |
| * Operating pressure = static pressure + pump pressure |
| ** Heat - resistant asbestfree gasket |
|
|
|
| |
|